Heavy duty, water cooled diesel engine
Radiator with mechanical fan
Protective grille for rotating and hot parts
Electric starter and charge alternator
Starting battery (with lead acid) including rack and cables
Engine coolant heater
Steel base frame and anti-vibration isolators
Spare external fuel tank (open set)
Flexible fuel connection hoses
Single bearing, class H alternator
Industrial exhaust silencer and steel bellows supplied separately
Static battery charger
Manual for application and installation
STANDARD SPECIFICATIONS
3 Phase Ratings, 50 Hz, PF 0,8
This generator set is manufactured in facilities certified to ISO 9001.
This generator set is available with CE certification.
This generator set has been designed to meet ISO 8528 regulation.
Enclosed product is tested according to EU noise legislation 2000/14/EC
400/230 1650,00 1429,00 1400,00 1200,00 2020,00
Standby Rating (ESP) Prime Rating (PRP)
Voltage kVA kW kVA kW Amp
Standby Rating (ESP): Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility source. ESP is in accordance
with ISO 8528. Overload is not allowed.
Prime Rating (PRP): Applicable for supplying power to varying electrical load for unlimited hours. PRP is in accordance with ISO 8528. 10 % overload capability is
available for a period of 1 hour within 12-hour perod of operation,in accordance with ISO 3046.
OPTIONAL EQUIPMENTS
TRANSFER SWITCH
- Three or four pole motor operated circuit breaker
- Three or four pole contactor
OTHER ACCESSORIES
- 1500/3000 hours maintenance kit
- Tool kit for maintenance
- Inlet and outlet acoustic baffles
- Double wall chassis
- Automatic transfer switch
- Main Fuel Tank
- Supplied with oil and coolant - 30 °C
- Low and high fuel level alarm
- Electrical oil drain pump
- Automatic or manual fuel filling system
- Residential silencer
- Inlet and outlet motorised louvers
- Duct adapter ( on radiator)
- Enclosure: weater protective or sound attenuated
CONTROL SYSTEM
- Remote communication with modem
- Alarm output relays
- Charge Ammeter
- Earth fault, single set
- Remote relay output
- Paralel system with mains.
- Automatic synchronising and power control system ( multi gen-set
Parallel )
- Remote annunciator panel
- Transition synchronization with mains
ENGINE
- Oil heater
- Fuel-Water Seperator Filter
- Remote Radiator Cooling
ALTERNATOR
- Main line circuit breaker
- Over sized alternator
- Anti-Condensation Heater
Commentaires sur ces manuels